Product Overview
Overview
The integrated absolute/pressure transmitter uses high-precision and high stability diffusion silicon isolation sensor components, which convert the absolute or gauge pressure of the measured medium into a 4-20mADC standard electrical signal through highly reliable amplification circuits and precision temperature compensation. The packaging technology and sophisticated assembly process ensure the excellent quality and performance of the product. This product has the characteristics of complete variety specifications, standardized interface forms, and convenient zero and range adjustment, which can meet the needs of customers to the fullest extent.
The CF2002 integrated transmitter series can be widely used in various harsh and dangerous places in industrial sites.
characteristics
Minimum measurement range above 5KPa
Measurement range: 0-32MPa
Direct process connection does not require installation of brackets
Zero point and external continuous adjustable range
Lightning protection and radio frequency interference prevention
With on-site instructions
Intrinsically safe explosion-proof or flameproof
Small size, beautiful appearance, high cost-effectiveness
High precision, high stability, high reliability overload pressure
2 times the range or 70 M P a (take the minimum value)
output signal
4-20 m A D C (two-wire system)
Working Voltage
14-36 (two-wire system) standard 24VDC ± 5%, ripple less than 1%
medium temperature
- 2 5~+ 1 0 0℃
ambient temperature
- 2 0~+ 8 5℃
relative humidity
0 %~1 0 0 %
Application
Industrial site process pressure detection and control
Laboratory pressure calibration system
Navigation and shipbuilding
Aviation and Aircraft Manufacturing
Air separation equipment and thermal power units
Energy Management System
Liquid level measurement and water supply system
Hydraulic and Pneumatic Control System
technical indicators
measuring medium
Various liquids, gases, or vapors compatible with 316L stainless steel
range
0-5 K P a to 0-3 2 M P a (see selection table) Load resistance
(4~20 m A) :R =(U-14)0.02-R0
Among them: U is the power supply voltage, R0 is the internal resistance of the cable
(0~10 m A) :R≤1KΩ
(0~5V) :R≥300Ω
Performance refers to standard accuracy
±0 . 1% (including comprehensive errors such as nonlinearity, repeatability, and hysteresis)
zero shift
Positive migration: 0% to+80% of the range Negative migration: 0% to -100% of the range (not exceeding -100 K Pa absolute pressure products without negative migration)
Range adjustment
Adjust the minimum range to any range (see selection table)
Overvoltage impact
Less than the range of 0 2 5 %
Power supply impact
Less than 0 of the output range 0 1 % V
Load impact
negligible
temperature effect
± 1 of the measuring range 5% (temperature range: -20 to+85 ℃, including the total temperature impact of zero and range)
stability
± 0 of the measuring range 2 5%/year structural characteristics membrane material
316L stainless steel
Joint material
1Cr18Ni9Ti stainless steel
housing material
1Cr18Ni9Ti stainless steel
process interface
M20 × 1.5, NPT1/2 or G1 external thread (large opening)
electrical interface
Standard waterproof plug
instruction table
nothing
weight
About 1.2kg
Explosion-proof marking
Exia Ⅱ CT5 (Ben An type) Exia Ⅱ CT5 (Explosion proof type)
The overall protective performance meets the following requirements:
IP67 (compliant with relevant parameters)